What type of equipment can be worked on with Type III certification? ✔✔low pressure
The most efficient method of leak checking a charged low-pressure refrigeration unit is
...
EPA Type III Questions and Answers
100% Pass
What type of equipment can be worked on with Type III certification? ✔✔low pressure
The most efficient method of leak checking a charged low-pressure refrigeration unit is to
✔✔pressurize the system by the use of controlled hot water or heater blankets
When pressurizing a system, do not exceed ✔✔10 psig
After reaching the required vacuum on an appliance when servicing, moisture is indicated by
✔✔multiple rises in pressure over a period of time with increase of pauses between rises
EPA required evacuation levels for recovery or recycling equipment manufactured or imported
before Nov. 15, 1993 is ✔✔25 inches Hg
EPA required evacuation levels for recovery or recycling equipment manufactured or imported
on or after Nov. 15, 1993 is ✔✔25 mm Hg absolute
What can be used to pressurize a chiller system before opening the system for a non-major
repair? ✔✔controlled hot water
Refrigerant recovery from a system using R-11 or R-123 starts with ✔✔liquid removal and is
followed by vapor recovery
If a strong odor is detected during the recovery process, ✔✔a compressor burn-out may have
occurred
When installing more than one, pressure relief valves must be installed ✔✔in parallel
The owner must keep records of refrigerant added during service and maintenance on equipment
✔✔with charges of 50 lbs. or greater
After all the liquid has been removed from an average 350 ton approximately how much vapor
refrigerant remains in the system ✔✔100 lbs.
When charging a system with a low pressure refrigerant should be introduced as a vapor to raise
saturation temperature to a minim of ✔✔36 degrees
Where is the purge unit located in a low-pressure system? ✔✔the top of the condenser
In a chiller, air and other noncondensables collect ✔✔at the top section of the condenser
A rupture disk for low pressure chiller will rupture at ✔✔15 psig
The Standard for machine room safety is ✔✔ASHRAE-15
Who establishes the refrigerant safety group standard ✔✔ASHRAE
A low pressure chiller used for comfort cooling must be repaired if it has an annual leak rate of
____ of the total charge. ✔✔15 percent
ASHRAE 34 Standard Safety classifies R-134a as ✔✔A1
Because a low-pressure system operates below atmospheric pressure (in a vacuum), ✔✔leaks in
the gaskets or fittings will cause air and moisture to enter the system
To repair a chiller operating with R-22 the technician ✔✔must have a Type II certification
What refrigerant has a safety classification of B-1? ✔✔HCFC 123 (R-123)
During evacuation of systems with large amounts of water, it may be necessary to ✔✔increase
pressure by introducing nitrogen to counteract freezing
When leak testing a low pressure chiller, the maximum pressure to use is ✔✔10 psig