Common standard time period for station battery to handle outage of AC power to chargers
8-12 hours
Time to restore data exchange redundancy when redundancy testing by RC/TOP/BA deemed unsuccessful
2 hours
Tr
...
Common standard time period for station battery to handle outage of AC power to chargers
8-12 hours
Time to restore data exchange redundancy when redundancy testing by RC/TOP/BA deemed unsuccessful
2 hours
Transition period to backup control facility (fully functioning)
2 hours
Annual testing of backup control facility must prove to be functional for this long
2 hours
Every 2 years TO/TOP/DSP must provide how many hours of system restoration training to field switching personnel
2 hours
Every 2 years GOP's with blackstart resources shall provide how many hours of training to operating personnel responsible for startup
2 hours
BAL-002 default contingency reserve restoration period (following disturbance recovery period)
90 minutes
How often should BA calculate and record inadvertent interchange
60 minutes/hourly
How often should BA provide MW-hour meter readings to adjacent BA's
60 minutes/hourly
TLR procedure (identifying TLR level and actions to be implemented) needs updating how often
60 minutes/hourly
Hourly ATC for next 48 hours calculated how often
60 minutes/hourly
During EEA2/3 the energy deficient entity needs to update the RC how often until alert is terminated
60 minutes/hourly
DOE-417 (disturbance reporting) should be completed by when
60 minutes
BA with loss of resources must submit RFI with start time no more than how far beyond the resource loss
60 minutes
Sink BA should ensure interchange modifications are submitted how soon after the modification
60 minutes
If unable to calculate ACE for this long, BA must notify RC
30 minutes
ACE cannot exceed BAAL for how long
30 minutes
If AVR, PSS, or other voltage control device status changes from normal operation, GOP must notify TOP within how long of the change (if it does not last longer than this, no reporting necessary)
30 minutes
GOP must notify TOP of change in reactive capability how quick
30 minutes
TOP should return from unknown operating state how quick
30 minutes
IROL Tv should be less than or equal to... (system should be returned to IROL within this time frame of exceeding)
30 minutes
RC completes RT assessments of SOL/IROL violations how often
30 minutes
Once BA/TOP notifies RC of emergency conditions, RC has how long to notify other BA/TOP's and neighboring RC's
30 minutes
Unplanned evacuation from BES control center facility is reportable by BA/TOP/RC if it lasts longer than...
30 minutes
Complete loss of communication (including backup) is reportable if it lasts longer than...
30 minutes
Planned or unplanned telemetering & control equipment outages of more than how many minutes but be reported
30 minutes
Default ramp rate for Western Interconnection interchange schedules
20 minutes
When BA unable to calculate ACE > 30 minutes, they have how long to report to RC
15 minutes
Default disturbance recovery period (time to return ACE to 0 following a disturbance, DCS)
15 minutes
Congestion management requests in Eastern Interconnection from one RC to another must be implemented how quickly
15 minutes
Voltage deviation of >/= 10% nominal is reportable after how long
15 minutes
Uncontrollable loss of firm load for how long is reportable (previous years peak demand >3000; >/+300mw - otherwise 200mw)
15 minutes
Transmission & generator data including status, output capability, output, phase angle settings, avr status, etc. should be updated every how many minutes
10 minutes
If BA denies interchange, they have how long to notify RC
10 minutes
Default ramp rate for for Eastern Interconnection interchange schedules
10 minutes
Unscheduled flow transmission relief requested by the TOP should be approved by the RC how quickly
5 minutes
Ramp for interchange schedules starts how soon before start of schedule
5 minutes
Multiple contingencies within how many minutes of each other are reported as a single contingency
1 minute
MW reportable threshold for sudden loss of gen
2000mw
Ace calculation occurs how often
6 seconds
When EEA3 is terminated, the EDE should submit a report to the RC how soon after termination/downgrading
2 business days
How often is ATC for next 31 days calculated
24 hours/daily
When a reportable threshold has been met, the responsible entity has how long to report
24 hours/next business day
GOP with blackstart resource must notify TOP of any change to capabilities affecting ability to meet restoration plan within how long of the change
24 hours
RC/BA/TOP should test primary control center data exchange capabilities for redundant functionality at least how often
90 calendar days
TOP should update and submit the restoration plan to the RC within how long after identifying unplanned permanent system modifications
90 calendar days
Changes to Operating plan with regards to backup facility should be updated/approved within how many days of the change
60 calendar days
TOP must provide copy of voltage schedule to RC or neighboring TOP's within how long of a request
30 calendar days
TOP must provide criteria used to develop voltage schedule or reactive power schedule to an inquiring GOP within how long of the request
30 calendar days
GO should provide tap settings/ranges and impedance data to TOP & transmission planner within how long of a request
30 calendar days
When BA/TOP submits Emergency Operating plan to RC, the RC has how long to review and notify of results
30 calendar days
RC has how long to approve/dissapprove TOP restoration plan
30 calendar days
GOP should provide blackstart test results to RC/TOP within how long of request
30 calendar days
RC should distribute revised restoration plans to each TOP & neighboring RC within how many days of revision/creation
30 calendar days
Conflicts between neighboring RC restoration plans should be resolved how quickly
30 calendar days
LSE, Transmission/Resource planners must share available amount of interruptible load & DCLM to TOP/BA/RC within how many days
30 calendar days
CPS-1 compliance factor is for how long of a period
12 months
CPS-1 measures the average frequency vs. NERC frequency target how often
1 minute
CPS-1 12 month compliance factor is evaluated how often
monthly
How often should BA check and calibrate time error and frequency devices against a common reference
12 months/annually
Minimally, BA/RSG's should review probable contingencies to determine MSSC how often
12 months/annually
Operating procedures should be reviewed by RC how often?
Annually, no more than 15 months
ATC for the next 12 months (months 2-13) should be calculated how often
Weekly
Operating plan contact information should be reviewed/validated how often
12 months/annually
RC backup facility functionality should be evaluated at least how often
12 months/annually
Operating personnel should be trained (documented) on restoration plan and procedures how often
12 months/annually
TOP should review and submit restoration plan to RC how often
12 months/annually
RC should conduct how many restoration drills each calendar year to include TOP/GOP's?
2
How long do you need to wait to reuse interchange tag numbers
12 months
System restoration plans/procedures for simulation should be tested and verified how often
At least every 3 years
How often are blackstart resources required to be tested
At least every 3 years
TOP should verify through analysis of actual events, steady state, and dynamic simulations/testing that the restoration plan accomplishes intended function how often
At least every 5 years
Zone 3 relays look at what percent of a line
150%
Zone 2 relays look at what percent of a line
120%
Zone 1 relays look at what percent of a line
90%
CPS-1 compliance factor requirement
at least 100%
DCS states that the BA should return ACE to 0 within the recovery period for what percent of reportable disturbances
100%
BA's frequency & ACE metering equipment should be available with a minimum accuracy of 0.001Hz for what percent of the year
99.5%
According to DCS, a contingency is considered a reportable disturbance if it is what percent of the MSSC
80%
Voltage deviation of what percent nominal voltage for extended period of time is reportable
10%
To restore 1Hz frequency, how much load would need to be shed
6-10%
During restoration, BES should be operated no more than what percent above or below nominal voltage profile
10%
During restoration, loads should be added in blocks not to exceed what percent of synchronized generating capability
5%
Good rule of thumb - frequency will sag 0.5Hz for what percent increase in load
5%
System wide voltage reduction of what percent is reportable for TOP
3%
Firm load shedding of how many MW (regardless if manually shed or auto shed) is reportable by the initiating entity
100mw
What time should planned outage information be reported by the TOP to the affected TOP/BA/RC?
1200
UFLS & UVLS threshold
300mw
When an entity makes a change to the documented CIP Senior Manager, it must be updated within how long
30 days
How soon is the selected unaffiliated third-party reviewing the TO/TOP security plan required to complete the review
90 days
If third-party reviewing TO/TOP security plan recommends changes, how long does the TO/TOP have to modify plan or provide reasons for no modifications
60 days
Alternative interpersonal communication capability testing should be completed how often by TOP/BA/RC
30 days/monthly
If alternative interpersonal communication testing is unsuccessful, how long does TOP/BA/RC have to initiate repair or replacement
2 hours
When is it required to notify entities of defective or non-working interpersonal communication capabilities
30 minutes
How long does TOP/RC/BA have to report communication capability failure
1 hour
How many hours of emergency operations training must each BA/TOP provide to their operating personnel
32 hours
B in ACE equation should be what percent of annual peak load
1%
How long must time error corrections last at minimum
1 hour
A generator must be equipped with a governor if it is over how many mw
10mw
What is the normal governor droop
5%
A governor is isochronous if the droop is what
0%
What is the minimum BAAL compliance score
90%