NFPA 10 Exam 127 Questions with Verified Answers
NFPA 10 - CORRECT ANSWER Standard for Portable Fire Extinguishers
NFPA 17 - CORRECT ANSWER Standard for Dry Chemical Extinguishing Systems
NFPA 17a - CORRECT ANSW
...
NFPA 10 Exam 127 Questions with Verified Answers
NFPA 10 - CORRECT ANSWER Standard for Portable Fire Extinguishers
NFPA 17 - CORRECT ANSWER Standard for Dry Chemical Extinguishing Systems
NFPA 17a - CORRECT ANSWER Standard for Wet Chemical Extinguishing Systems
Portable fire extinguishers - CORRECT ANSWER The first line of defense to cope with fires of limited size
Authority Having Jurisdiction (AHJ) - CORRECT ANSWER An organization, office, or individual responsible for enforcing the requirements of a code or standard, or for approving equipment, materials, an installation, or a procedure.
Approved - CORRECT ANSWER Acceptable to the authority having jurisdiction.
ANSI - CORRECT ANSWER American National Standards Institute
carbon dioxide - CORRECT ANSWER A colorless, odorless, electrically non-conductive gas that is suitable for extinguishing class B and C fires.
Dry Chemical - CORRECT ANSWER A powder composed of very small particles, usually sodium bicarbonate-,potassium bicarbonate-, or ammonium phosphate based with added particulate material supplemented by special treatment to provide resistance to packing, resistance to moisture absorption (caking), and the proper flow capabilities
Wet Chemical - CORRECT ANSWER Normally an aqueous solution of organic or inorganic salts or a combination thereof that forms an extinguishing agent
High Pressure Cylinder - CORRECT ANSWER Cylinders or cartridges containing nitrogen, compressed air, carbon dioxide, or other gases at a pressure higher than 500psi at 70°F.
low pressure cylinder - CORRECT ANSWER Cylinders containing fire-extinguishing agent, nitrogen, compressed air, or other compressed gases at a service pressure of less than 500psi at 70°F.
Fire extinguisher inspection - CORRECT ANSWER Quick check that the fire extinguisher is in it's designated place, that it has not been actuated or tampered with, and that there is no obvious physical damage or condition Tom prevent its operation.
Fire extinguisher maintenance - CORRECT ANSWER A thorough examination of the fire extinguisher that is intended to give maximum assurance that a fire extinguisher will operate effectively and safely and to determine if physical damage or condition will prevent its operation , if any repair or replacement is necessary, and if hydrostatic testing or internal maintenance is required.
Shall - CORRECT ANSWER Indicates a mandatory requirement.
Should - CORRECT ANSWER Indicates a recommendation or that which is advised but not required.
Extinguishers manufactured after this date must include the identification of the listing and labeling organization, the fire test standard, and the performance standard that the fire extinguisher meets or exceeds. - CORRECT ANSWER January 1st, 1986
Class A fire - CORRECT ANSWER Ordinary combustibles
Class B fires - CORRECT ANSWER Flammable Liquids
Class C fires - CORRECT ANSWER Contain an energized electrical component
Class D fires - CORRECT ANSWER Contain combustible metals
Class K fires - CORRECT ANSWER Fires in cooking appliances that involve combustible cooking
media (vegetable or animal oils and fats).
Class K fire extinguishers manufactured after this date shall not be fitted with "extended wand-type" discharge devices - CORRECT ANSWER January 1st, 2001
Only extinguishers of this type shall be installed in areas containing oxidizers (such as pool chemicals) - CORRECT ANSWER Water-type
Where shall fire extinguishers be located? - CORRECT ANSWER In a conspicuous location near the path of egress
Fire extinguishers having a gross weight not exceeding ______ shall be installed so that the top of the fire extinguisher is not more than _____ from the floor. - CORRECT ANSWER 40 lb, 5 ft
Fire extinguishers having a gross weight greater than ______ shall be installed so that the top of the fire extinguisher is not more than _____ from the floor. - CORRECT ANSWER 40 lbs, 3.5ft
In no case shall the clearance between the bottom of the fire extinguisher and the floor be less than _____. - CORRECT ANSWER 4 in
The minimum rated single extinguisher for a light hazard occupancy for class A hazards is: - CORRECT ANSWER 2A
The minimum rated single extinguisher for a normal hazard occupancy for class A hazards is: - CORRECT ANSWER 2A
The minimum rated single extinguisher for an extra hazard occupancy for class A hazards is: - CORRECT ANSWER 4A
A class A fire extinguisher protecting a light hazard occupancy will cover ______ per unit of A. - CORRECT ANSWER 3000sqft
A class A fire extinguisher protecting a normal hazard occupancy will cover ______ per unit of A. - CORRECT ANSWER 1500sqft
A class A fire extinguisher protecting an extra hazard occupancy will cover ______ per unit of A. - CORRECT ANSWER 1000sqft
Fire extinguishers protecting a class D hazard shall not be located further away than - CORRECT ANSWER 75ft
Fire extinguishers protecting a class D hazard shall not be located further away than - CORRECT ANSWER 75ft
Fire extinguishers must be inspected at least every ______ - CORRECT ANSWER 31 days
Fire extinguishers must be inspected at least every ______ - CORRECT ANSWER 31 days
UL 1093 - CORRECT ANSWER Standard for Halogenated Agent Fire Extinguishers
UL 1803 - CORRECT ANSWER Standard for Factory Follow-Up on Third Party Certified Portable Fire Extinguishers
UL 8 - CORRECT ANSWER Water Based Agent Fire Extinguishers
UL 154 - CORRECT ANSWER Standard for Carbon Dioxide Fire Extinguishers
UL 299 - CORRECT ANSWER Standard for Dry Chemical Fire Extinguishers
UL 626 - CORRECT ANSWER Standard for Water Fire Extinguishers
UL 711 - CORRECT ANSWER Standard for Rating and Fire Testing of Fire Extinguishers
UL 2129 - CORRECT ANSWER Standard for Halocarbon Clean Agent Fire Extinguishers
Light hazard minimum B rating for 30ft distance - CORRECT ANSWER 5 B
Light hazard minimum B rating for 50ft distance - CORRECT ANSWER 10 B
Normal hazard minimum B rating for 30ft distance - CORRECT ANSWER 10 B
Normal hazard minimum B rating for 50ft distance - CORRECT ANSWER 20 B
Extra hazard minimum B rating for 50ft distance - CORRECT ANSWER 80 B
Extra hazard minimum B rating for 30ft distance - CORRECT ANSWER 40 B
2-A Extinguisher Equivalent - CORRECT ANSWER Two 1-A water-types
Maximum floor area coverage for any A rated extinguisher - CORRECT ANSWER 11,250sqft
For Flammable Liquids of Appreciable Depth, how many units of B are needed per sqft of surface area? - CORRECT ANSWER 2 units, except AFFF and FFFP, then 1 unit.
Internal exam interval for stored-pressure loaded stream and antifreeze - CORRECT ANSWER 1 year
4-A Extinguisher Equivalent - CORRECT ANSWER Two 2.5gal water-types
Internal exam interval for pump tank water and pump tank, calcium chloride based - CORRECT ANSWER 1 year
Internal exam interval for dry chemical, cartridge- and cylinder-operated, with mild steel shells - CORRECT ANSWER 1 year
Internal exam interval for dry powder, cartridge- and cylinder-operated, with mild steel shells - CORRECT ANSWER 1 year
Internal exam interval for stored-pressure water - CORRECT ANSWER 5 years
Internal exam interval for AFFF and FFFP - CORRECT ANSWER 3 years
Internal exam interval for wetting agent - CORRECT ANSWER 1 year
Internal exam interval for stored-pressure dry chemical, with stainless steel shells - CORRECT ANSWER 5 years
Internal exam interval for carbon dioxide - CORRECT ANSWER 5 years
Internal exam interval for wet chemical - CORRECT ANSWER 5 years
Internal exam interval for dry chemical stored-pressure, with mild steel shells, brazed brass shells, and aluminum shells - CORRECT ANSWER 6 years
Internal exam interval for halogenated agents - CORRECT ANSWER 6 years
Internal exam interval for dry powder, stored-pressure, with mild steel shells - CORRECT ANSWER 6 years
Hydrostatic testing interval for stored-pressure water, water mist, loaded-stream, and/or antifreeze - CORRECT ANSWER 5 years
Hydrostatic testing interval for wetting agent - CORRECT ANSWER 5 years
Hydrostatic testing interval for AFFF and FFFP - CORRECT ANSWER 5 years
Hydrostatic testing interval for dry chemical with stainless steel shells - CORRECT ANSWER 5 years
Hydrostatic testing interval for carbon dioxide - CORRECT ANSWER 5 years
Hydrostatic testing interval for wet chemical - CORRECT ANSWER 5 years
Hydrostatic testing interval for dry chemical, stored-pressure, with mild steel shells, brazed brass shells, or aluminum shells - CORRECT ANSWER 12 years
Hydrostatic testing interval for dry chemical, cartridge- or cylinder-operated, with mild steel shells - CORRECT ANSWER 12 years
Hydrostatic testing interval for halogenated agents - CORRECT ANSWER 12 years
Hydrostatic testing interval for dry powder, stored-pressure, cartridge- or cylinder-operated, with mild steel shells - CORRECT ANSWER 12 years
Hydrostatic testing pressure gauges must be accurate within +/-_____ of the full range of the gauge - CORRECT ANSWER 0.5%
Hydrostatic gauges shall be capable of indicating ____ to _____ of the test pressure - CORRECT ANSWER 90%, 110%
Hydrostatic gauge test pressures shall be capable of being read to within ____ of the test pressure. - CORRECT ANSWER 1%
Hydrostatic testing pressure gauges shall be calibrated at least _____ - CORRECT ANSWER Semiannually
Master gauges or dead weight testers shall be calibrated at least _____ - CORRECT ANSWER Annually
A hydrostatic test pump shall be capable of producing not less than _____ of the test pressure - CORRECT ANSWER 150%
Temperatures used for drying shall not exceed _____ - CORRECT ANSWER 150°F
The pressure in a hydrostatic test of a cylinder shall be maintained for a minimum of - CORRECT ANSWER 30 seconds
The pressure in a hydrostatic test of a hose assembly shall be applied at a rate of rise such that the test pressure is reached in - CORRECT ANSWER 1 minute
The pressure in a hydrostatic test of a hose assembly shall be maintained for a minimum of - CORRECT ANSWER 1 minute
Test pressure for stored pressure types - CORRECT ANSWER As labeled, or where not specified, to factory test pressure, not to exceed 3x service pressure.
Test pressure for cartridge operated types - CORRECT ANSWER At original factory pressure as shown on nameplate or shell
Test pressure for DOT 3A, 3AA, or 3AL cylinders - CORRECT ANSWER 5/3 service pressure
Test pressure for ICC3 cylinders - CORRECT ANSWER 3000 psi
Test pressure of carbon dioxide hose assembly - CORRECT ANSWER 1250 psi
Test pressure for low-pressure accessory hose on wheeled extinguisher - CORRECT ANSWER 300 psi
Test pressure for dry chemical, dry powder, water, foam, and halogenated agent hose assemblies - CORRECT ANSWER 300 psi, or service pressure, whichever is higher
Test pressure for high-pressure accessory hose on wheeled extinguisher - CORRECT ANSWER 3000 psi
The record of a hydrostatic test shall be maintained by the organization that performed the test until either - CORRECT ANSWER The expiration of the test period or until the cylinder is again tested
Compressed air used to recharge fire extinguishers shall have a maximum dew point of - CORRECT ANSWER -60°F
Nitrogen used to recharge fire extinguishers shall have a maximum dew point of - CORRECT ANSWER -60°F
Argon used to recharge fire extinguishers shall have a maximum dew point of - CORRECT ANSWER -65°F
A regulated source of pressure, set no more than _____ above the operating pressure, shall be used to pressurize fire extinguishers. - CORRECT ANSWER 25 psi
The gauge used to set the regulated source of pressure shall be calibrated at least - CORRECT ANSWER Annually
The vapor phase of carbon dioxide shall not be less than _____ carbon dioxide - CORRECT ANSWER 99.5%
The water content of carbon dioxide shall not be more than _____ by weight at _____ dew point - CORRECT ANSWER 60ppm, -52°F
Oil content of carbon dioxide shall not be more than _____ by weight - CORRECT ANSWER 10ppm
The agent in pump tank water and pump in tank calcium chloride-based antifreeze types shall be replaced - CORRECT ANSWER Annually
The agent in pump tank water and pump in stored pressure wetting agent types shall be replaced - CORRECT ANSWER Annually
The agent in AFFF and FFFP types shall be replaced - CORRECT ANSWER Every 3 years
A carbon dioxide hose assembly electrical conductivity test shall be conducted - CORRECT ANSWER Annually
Millimeter - CORRECT ANSWER 1 in. = 25.4 mm
NFPA 32 - CORRECT ANSWER Standard for dry cleaning plants 2007
high pressure cylinders - CORRECT ANSWER Cylinders containing nitrogen, compressed air, carbon dioxide or other gases at a pressure HIGHER then 500 psi 70 degrees F.
Low-Pressure cylinders - CORRECT ANSWER Cylinders filled with gas 500 psi or LOWER @ 70 degrees F.
Extinguisher service pressure - CORRECT ANSWER Normal operating pressure as indicated on the nameplate or cylinder of a fire extinguisher.
Factory test pressure - CORRECT ANSWER Pressure shown on the nameplate at which a shell was tested at time of manufacture.
Wetting agent - CORRECT ANSWER When added to water, reduces surface tension and increases its ability to penetrate and spread.
Dry chem. extinguishers manufactured prior to _________ seal be removed from service at next 6 year maintenance interval or next hydro test (unless wheeled-type dry chem.) - CORRECT ANSWER October 1984
Wheeled fire extinguishers shall be considered when: - CORRECT ANSWER 1) High hazard areas
2) Limited personal available, extinguisher should have:
-High agent flow rate
-Increased agent stream range
-Increased agent capacity
Low Hazard Occupancy Rating - CORRECT ANSWER -Levels of A and B combustibles are low.
-Normal levels of A or less then 1 gal. of class B
Ordinary (moderate) Hazard Occupancy Rating - CORRECT ANSWER -Moderate levels of A and B combustibles
-Moderate levels of A or 1-5 gal of B
Extra (high) hazard Occupancy rating - CORRECT ANSWER - High A/B combustibles
- More then 5 gal of B in any room
Travel distance for portable fire extinguishers shall not exceed.... - CORRECT ANSWER 50 ft.
In class D hazards, extinguisher or extinguisher agent shall be located no more then ________ away from class D hazard. - CORRECT ANSWER 75 ft.
In class K fire extinguishers, travel distance to extinguisher shall not exceed ______ from hazard. - CORRECT ANSWER 30 ft.
Internal inspection - CORRECT ANSWER 6 years
Minimum size label for carbon dioxide hose test pass? - CORRECT ANSWER 0.5 in. x 3 in.
[Show More]