TFM 12 Fire Alarm Technical Test
Does a fire hood system and a kitchen need to be monitored by the fire alarm system? - ✔✔Yes
What does P.L.F.A stand for? - ✔✔Power Limited Fire Alarm
What does N.P.L.F.A stand for? -
...
TFM 12 Fire Alarm Technical Test
Does a fire hood system and a kitchen need to be monitored by the fire alarm system? - ✔✔Yes
What does P.L.F.A stand for? - ✔✔Power Limited Fire Alarm
What does N.P.L.F.A stand for? - ✔✔Non-Power Limited Fire Alarm
What is the difference between P.F.L.A and N.P.F.L.A? - ✔✔an N.P.L.F.A can operate at up to
600v, and the power output isn't limited
a P.L.F.A has the voltage and power limited by a listed power source.
What material must N.P.F.L.A circuit conductors be made from? - ✔✔ONLY solid stranded
copper is permitted.
What does A.W.G stand for? - ✔✔American Wire Gauge
What size conductors are permitted? - ✔✔Size 18 A.W.G and 16 A.W.G are permitted, provided
they do not exceed certain capacities.
What is used to protect transformers or other devices supplied from power-supply conductors? -
✔✔An over-current device not rated over 20 amperes.
When located within 7 feet of the floor, how shall cables be fastened? - ✔✔Cables shall be
fastened in an approved manner at intervals of not more than 18 inches.
Single conductors shall not be smaller than ___ A.W.G? - ✔✔18
Conductors of 28 A.W.G shall only be permitted in which circumstance? - ✔✔Spliced with a
connector listed as suitable for 26 to 24 A.W.G
How shall P.F.L.A conductors NOT be installed? - ✔✔P.F.L.A conductors shall not be strapped,
taped, or attached to the exterior of any conduit or raceway.
What is Plenum cable? - ✔✔Cable that can be installed in ducts, plenums, or other spaces used
for environmental air.
What is a Riser cable? - ✔✔Cable to be used in vertical wire runs in shafts between floors. Not
to be used where Plenum cable is required.
It is capable of preventing fire from rising from floor to floor.
What is general purpose cable? - ✔✔Cable for general purpose fire alarm use. Not to be used
where plenum cable or riser cable is required.
It is resistant to the spread of fire.
Why 'type' shall plenum cable be? What substitutions are allowed? - ✔✔Power Limited Fire
Alarm Plenum (F.P.L.P) C.M.P can be substituted.
Why 'type' shall riser cable be? What substitutions are allowed? - ✔✔Power Limited Fire Alarm
Riser (F.P.L.R) C.M.P, F.P.L.P.
C.M.R can be substituted.
What 'type' shall general purpose wire be? What substitutions are permitted? - ✔✔Power
Limited Fire Alarm (F.P.L) C.M.P, F.P.L.P, C.M.R, F.P.L.R, C.M.G
CM can be substituted (all types)
What is the maximum voltage permitted through multi-conductor N.P.F.L.A cables? - ✔✔150
volts
What is the voltage rating marked on P.F.L.A cables? - ✔✔Not less than 300 volts
Shall the voltage rating marked on P.F.L.A cables? - ✔✔No, because they may be mistakenly
used for electrical applications.
What is 'Rate Compensation Detector'? - ✔✔A device that responds when a temperature rises at
an exceeding rate that is predetermined.
What is a 'Smoke Detector'? - ✔✔a device that detects both visible and invisible combustion
particles?
Which detector is best a detecting invisible particles? - ✔✔Ionization
Which sensor is better at detecting thick, visible smoke particles? - ✔✔Photoelectric
What is a SPOT TYPE sensor? - ✔✔a device in which detecting an element is concentrated at a
particular location.
What is a DIGITAL ALARM COMMUNICATOR TRANSMITTER ( D.A.C.T)? - ✔✔A
system component at the protected premises is connected to the detection devices. It has a line
seizure and can connect to a D.A.C.R.
What is a DIGITAL ALARM COMMUNICATOR RECEIVER? (D.A.C.R)? - ✔✔A system
component that accepts and displays signals sent over the public phone network from a D.A.C.T
(i.e A.D.T monitoring center)
What is an alarm signal? - ✔✔A signal indicating an emergency that requires immediate action.
What is a Supervisory signal? - ✔✔A signal that indicates the need for action in connection with
the SUPERVISION of fire equipment.
What is a Trouble signal? - ✔✔A signal that indicates a fault with the fire equipment. It must
have an audible signal, distinctive from alarm signals.
Does an exterior harm for a sprinkler system need to be supervised? - ✔✔Yes
What is a Cloud Chamber Smoke detection? - ✔✔A detector draws an air sample into a high
humidity, low pressure chamber. The conditions in the chamber cause the moisture in the air to
condense on the smoke particles, forming a cloud. The density of this cloud is measured by a
photoelectric principle, if it meets a certain criteria, an alarm is generated.
What is an Ionization Smoke detector? - ✔✔A detector that used a small amount of radio active
material to ionize the air between two differently charged electrodes. When smoke is present
between these electrodes, it causes the conductance of the air to decrease, and this causes the
alarm to trip.
What is Photo Electric Light Scattering Smoke Detection? - ✔✔A detector that uses a light
source and a photosensitive sensor, arranged so that light will only fall on the sensor when
smoke particles are present. The particles reflect and retract light towards the sensor, tripping the
alarm.
What is important about the way trouble signals sound? - ✔✔They must be distinctive from
alarm signals.
What three procedures must be in place before it is permitted to install a means to silence
trouble/supervisory/alarm signals? - ✔✔The means shall be key operated and contained within a
locked enclosure
The means shall transfer it's audible warning to a visual warning.
The audible trouble signal shall sound when the system is set to silent mode and no trouble or
supervisory exists.
Fire/supervisory signals shall be ____ in sound from other signals and shall not be used for any
other purpose. - ✔✔Distinctive
What code shall all wiring, cable and equipment be in accordance with? - ✔✔NFPA 70, National
Electric Code, Specifically articles 760, 770, and 800.
All systems shall test free of _______, except for application in which _______ are approved. -
✔✔grounds, grounds
So long as a single open, ground, or short circuit conditioned do not affect the operation
equipment, what is not needed? - ✔✔Monitoring for integrity, such conditions must not prevent
alarm, trouble or supervisory signals being sent.
If speakers are used to generate audible fire signals, What rule must apply? - ✔✔The speaker
must be monitored for integrity, and failure should result in a trouble signal.
Where must a spot type heat and smoke sensors be located on walls and ceilings? - ✔✔On the
ceiling- not less than 4 inches from the sidewall.
On the wall- between 4 inches and 12 inches from the ceiling.
When more than one detector is used on a ceiling, what spacing measurement shall be used? -
✔✔All points shall have a detector equal to 0.7 times the listed spacing.
When water flow occurs that is equal or greater than the flow of a single sprinkler, how quickly
shall the alarm signal initiate? - ✔✔Within 90 seconds
Can detectors be installed within an air duct system? Can they be used as a substitute for open
area protection? - ✔✔Yes and No
Detectors shall be ________ for the purpose for which they are being used. - ✔✔Listed (i.e zone
listed)
Which signals must take priority over all other signals? - ✔✔Fire. Even if a non fire signal is
generated first.
How many fire alarm boxes (pull stations) are required in systems employing automatic fire or
water flow detectors? - ✔✔At least one, located where required by the authority having
jurisdiction.
Systems that require two automatic detectors to initiate the alarm may only be used after which 3
conditions are filled? - ✔✔The systems are not prohibited by the AHJ.
At least two automatic detectors are in each protected space.
The alarm verification feature is not used.
The number of water flow switches permitted to be connected to a single initiating device shall
not exceed ________. - ✔✔5
What must be monitored for integrity? - ✔✔the installation wiring between the fire alarm control
unit and the relay or other appliance.
(Horn, Strobe, etc.)
Each elevator lobby, elevator hoist way and elevator machine room detector must be capable of
what? - ✔✔initiating elevator recall.
Must the alarm devices within the elevator hoist way be integrated with the fire alarm? - ✔✔Yes
Wall mounted appliances must be located between which two distances above a finished floor? -
✔✔Not less than 80 inches and not greater than 96 inches above the finished floor.
When may the manual testing frequency be extended to annually? - ✔✔if automatic testing is
performed at least weekly.
The responsibility for inspections, tests, and maintenance programs shall be assigned by the
_______ to a designated person of authority. - ✔✔Owner
Room sizes and contours, airflow patterns, obstructions, and other characteristics of the _______
shall be taken into account. - ✔✔Protected Hazard
Circuits for transmission of supervisory signals shall ____ alarm circuits. - ✔✔Ran separate
from
Household smoke alarm and smoke detectors installed within a _______ horizontal path of a
cooking appliance shall be equipped with an alarm-silencing means or be of the photo electric
type. - ✔✔20 feet
Each household heat detector, including a heat detector integrally mounted on a smoke detector,
shall detect abnormally high temperature or rate-of-temperature rise and all detector shall be
listed or approved for not less than ______ feet between detectors. - ✔✔50 feet
In a combination system, a _____ signal shall take precedence or bo clearly recognizable over
any other signal. - ✔✔Fire alarm
One of the most critical factors of any fire alarm system is the _____ the fire detecting devices. -
✔✔Location of
A circuit or path connecting a subsidiary station to a supervising station over which signals are
carried is called a _______. - ✔✔Communications channel
If batteries are used a source of energy, they shall be replaced ________. - ✔✔As recommended
The total sound pressure level produced by combining the ambient sound pressure level with all
audible notification appliances operating shall not exceed ________ in the occupiable area. -
✔✔110 dBA
Permanent records (such as As-Built installation drawings, operation and maintenance manuals,
a written sequence of operation and site specific software) shall be retained by the system owner
or the owners representative for how long? - ✔✔Life of the system
Spot-type smoke detectors mounted on the side wall should have the top of the detector between
_____ inches from the ceiling. - ✔✔4 and 12
Smoke detectors shall be installed (3) _______. - ✔✔Outside each separate sleeping area
In basements
On each additional story of the family living unit.
Household fire alarm systems shall have two independent power sources consisting of a primary
source that uses commercial light and power, and a secondary source consisting of _______. -
✔✔Rechargeable batteries
May an audible trouble signal be permitted to be common to several supervised circuits? -
✔✔Yes!
The maximum allowable time lapse from the initiation of a single fire alarm signal until it is
recorded at the supervising station shall not exceed 90 seconds. When any number of subsequent
fire alarm occur at any rate, they shall be recorded at a rate no slower than one every additional
________ seconds. - ✔✔10
When the runner is not in attendance at the proprietary supervising station, the runner shall
establish two way communications with the station at intervals not exceeding ________ minutes.
- ✔✔15
Automatic alarm initiating systems equipped with alarm verification features shall be permitted
provided (4) _____. - ✔✔1- Alarm verification feature in not initially enabled unless conditions
or occupant activities are expected that cause nuisance alarms.
2- A smoke detector that is continuously subjected to smoke concentration above alarm threshold
does not delay system functions more than 1 minute.
3-Actuation of an alarm device other than smoke detector causes the system functions without
additional delay. (not 10 seconds)
4-Current status of the alarm verification feature is shown on the record of completion.
Where both coded sprinkler supervisory signals and coded fire or water flow alarm signals are
transmitted over the same circuit, provision shall be made to either obtain (2) ______ of the fire
alarm signal, to prevent the loss of an alarm signal. - ✔✔Sufficient repetition
Alarm signal precedence
Connections to the light and power service shall be on a _______ branch circuit. - ✔✔dedicated
Each manual fire alarm box shall be securely mounted. The operable part of the box shall not be
less than _____ and not more than _____ above the floor level. - ✔✔3 1/2 feet
4 1/2 feet
All apparatus shall be restored to normal _____ after each test or alarm. - ✔✔As promptly as
possible
A _________ is a local signaling system for fire alarm, supervisory or guard's tour supervisory
services for household fire warning systems, whose components may be used in whole or in part
in common with a non-fire signaling system. - ✔✔Combination system
A means for turning off an activated alarm notification appliance shall be permitted only if
_________. - ✔✔The means must deactivate both the audible and visible notification appliances
simultaneously.
If speakers are used to produce audible fire alarm signals, trouble signals are required to be
displayed under which condition? - ✔✔When an amplifier fails and the system is in alarm and
operating on secondary power source.
Local protective systems of the electrical type must test free of grounds. - ✔✔True
Audible signal appliances intended for use in special environments such as (4) _______ or where
subject to tampering shall be listed for the intended application. - ✔✔Outdoors versus indoors
high humidity
dusty conditions
hazardous locations
When common wiring is employed for ________ the equipment for other than fire alarm
signaling system use shall be connected to the common wiring of the system in such a manner
that short circuits, or open circuits, or grounds in this equipment or between this equipment and
the fire alarm system wiring, will not interfere with either the supervision of the fire system or
prevent alarm or supervisory signal transmission. - ✔✔Combination system.
A pressure tank supervisory signal initiating device for a pressure tank shall detect both high and
low pressure conditions. A signal shall be obtained when the pressure is increased or decreased
______ psi from the required pressured value. - ✔✔10
Homeowners shall test systems in accordance with the manufacturer's instructions and shall have
every residential fire alarm system tested by a qualified service technician at least every _____. -
✔✔3 years
Manually actuated alarm-initiating devices shall (3) _____. - ✔✔1. Be used only for FA
initiating purposes and guards tour signaling.
2. Have the operable part of the manual FA box mounted between 3 1/2 and 4 1/2 above floor
level.
3. Be mounted within 5 feet of the exit doorway opening at re-exit on each floor.
In a protected premises FA system the secondary power supply shall automatically supply the
energy to the system within _______ seconds whenever the primary power supply is incapable. -
✔✔10
When the same sound is used for both supervisory and trouble signals, distinction between
signals shall be by other appropriate means such as visible annunciation. - ✔✔True
A switch for silence in the signal sounding appliance shall be permitted if it transfers the trouble
indication to a lamp or other acceptable visible indicator adjacent to the switch. - ✔✔True
Automatic FA signal initiating devices that have integral trouble _____ shall be connected to the
initiating device circuit so that a trouble condition within a device does not impair alarm
transmission from any other initiating device. - ✔✔Signaling contacts